JAKSA Solenoid Valves

2/2 PULSE SOLENOID VALVES
for dust collectors and soot removal

1" - 6/4"


Pulse (or shock) valves are used both in dust clean blowing systems for pulse bag filters, and in boiler soot removal systems. The main characteristics of pulse valves are large flow capacity and extremely short opening time (around 5 ms). These result in powerful sonic shock wave which efficiently removes dust particles (bag filters) or sediments in boiler tubes. Our valves are designed for long and reliable operation with minimum maintenance.

JAKSA Pilot-Operated Solenoid Valves

TECHNICAL DATA:

  • Internal parts: brass, stainless steel
  • Seals: NBR
  • Fluid temperature: -10°C to +85°C
  • Ambient temperature: max +55°C
  • Viscosity: max 21 mm2/s
  • Response times: opening 5 ms; closing 100 ms
  • Voltage: 230, 115, 48, 24 V AC; 24, 12 V DC
  • Duty cycle: continuous (ED100%)
  • Cycling rate: 10 - 100 cycles/min
  • Electrical protection: IP65 (with plug to ISO 6952 / ISO 4400)
    Long term use in humid environment requires the use of sealing sets.

Closed when de-energised (NC) Fluid symbol

Ports Orifice size
[mm]
Kv
(water at 1bar)
[l/min]
Differential pressure
[bar]
Body Mass
[kg]
Coil type Model Order code
(click for details)
Fig.
min max
G1 25 180 0.3 8 Brass 1.2 TM30 M260Y 362865 1
G6/4 40 350 0.3 8 Brass 2.75 TM30 M270Y 372865 2

OPTIONS:

Download/print PDF